| RXP 210: Air-volume alarm unit
Areas of application Monitoring laboratory fume cupboard as per EN14175 in combination with an air-volume controller, type RLP100 F123, and the RXP 212 fume cupboard operating unit. Zone 1 potentially explosive areas.
Properties
- Comparison of sash opening setpoint with actual value of air volume
- Feeding setpoint difference to alarm unit
- Acoustic alarm in the event that the actual value falls below or exceeds the specified value
- Thermoplastic housing suitable for wall or top-hat rail mounting (rail EN 60715)
- Compressed-air connections with Rp 1/8" female thread
- Low-pressure connections in form of stepped nipples for flexible plastic hose (internal Ø 4 and 6 mm)
- ATEX certification for use in Zone 1 potentially explosive areas
- Conformity tested as per EN 13463-1 and EN 1127-1 (Ex II 2 G T6)
- Complies with directive 97/23/EC Art. 3.3 on pressure equipment
Technical description
- Supply pressure 1.3 bar ± 0.1
- Response sensitivity 1%
|