RLP 100 F9..: Dual-channel air-volume controller

How energy efficiency is improved
For demand-led volume flow control of dual-channel systems in offices.

Areas of application
Room air-conditioning using VAV in dual-channel ventilation systems.

Properties

  • Optimal use of energy thanks to RLP 100 dual-channel controller in combination with room control equipment in the TSP, TSFP, TSSP series
  • Can be combined with virtually all mixing boxes currently on the market
  • ATEX certification for use in Zone 1 potentially explosive areas
  • Conformity tested as per EN 13463-1 and EN 1127-1 (Ex II 2 G T6)
  • Control of constant, switchable or variable air volumes
  • Highly accurate, static differential pressure sensor with large measuring range (1 to 160 Pa)
  • Controller front panel is printed with circuit diagram for rapid identification of function
  • Glass-fibre-reinforced thermoplastic housing suitable for wall or top-hat rail mounting (rail EN 60715)
  • Compressed-air connections with Rp 1/8" female thread
  • Special measuring connection for recording the volume flow with M4 connector
  • Low-pressure connections in form of stepped nipples for flexible plastic hose (internal Ø 4 and 6 mm)
  • Complies with directive 97/23/EC Art. 3.3 on pressure equipment


Technical description

  • Supply pressure 1.3 bar ± 0.1
  • Response sensitivity of sensor 0.1 Pa
  • Linearity, square root extraction accuracy 2%
  • Two inputs for:
    • command variable
    • day/night changeover or heating/cooling signal
  • Three outputs for:
    • actual value of air volume
    • activation of two damper drives, heating and cooling
  • Adjuster for adjustment of the sensor measuring range
  • Two setpoint adjusters for maximum and minimum limiting of volume flow

Type

Title

RLP100F910

Pneum volume-flow contr.fixed value, 2-c hannel

RLP100F916

Pn.vol.flowcontr.dual-ductfixed setpoint

RLP100F918

Pn.vol.flowcontr.dual-ductvariabel